Product Introduction
The Yokogawa ADV551-P03 is a high-performance Digital Output (DO) module designed specifically for use with the Yokogawa CENTUM VP Distributed Control System (DCS). As part of the N-IO (Network I/O) subsystem, it provides reliable and accurate digital output control capabilities in industrial automation environments.
Engineered to meet the demands of modern process control, the ADV551-P03 module offers 32 channels of digital output, ensuring flexible deployment in applications where multiple binary control signals are required. Each channel is independently isolated, providing a high level of reliability and safety, particularly in critical process environments such as oil & gas, petrochemical, power generation, and pharmaceuticals.
Product Specifications
| Parameter | Specification |
|---|---|
| Model Number | ADV551-P03 |
| Product Type | Digital Output Module |
| Channels | 32 channels (sink type) |
| Output Type | Open collector (24 V DC nominal) |
| Output Current | 0.5 A per channel (max) |
| Isolation | Photocoupler isolation between channels and system |
| Update Time | ≤ 100 ms |
| Power Supply Voltage | Supplied via base plate |
| Power Consumption | Approx. 4.8 W |
| Diagnostic Functions | Channel failure detection, module failure detection |
| Operating Temperature | 0 to 55°C |
| Storage Temperature | -20 to 70°C |
| Relative Humidity | 5% to 95% RH (non-condensing) |
| Installation | Mounted on base plate in system cabinet |
| Dimensions (W×H×D) | 107.5 × 130 × 32.8 mm |
| Weight | 0.2 kg |
| Compatible Systems | CENTUM VP, ProSafe-RS |
Applications
The ADV551-P03 module is ideal for a wide range of discrete and batch control applications, including:
-
Process Automation: Used in large-scale plants for controlling pumps, fans, and motor starters.
-
Building Automation: Integration with building management systems for lighting and HVAC control.
-
Water & Wastewater Treatment: Reliable digital control of valves and actuators.
-
Power Plants: Control of turbine auxiliaries and emergency shutdown systems.
-
Oil & Gas Industry: Used in DCS configurations for wellhead and pipeline automation.
-
Pharmaceutical Manufacturing: Batch control processes and cleanroom automation.
Product Advantages
-
High Channel Density: 32 digital output points reduce the number of modules required, saving space and cost.
-
Robust Isolation: Each channel is isolated to protect system integrity and improve fault tolerance.
-
Diagnostic Capability: Advanced self-diagnostics minimize downtime and simplify maintenance.
-
Seamless Integration: Designed to operate smoothly with Yokogawa’s flagship CENTUM VP DCS.
-
Long Lifecycle Support: Backed by Yokogawa’s extensive lifecycle services and long-term availability commitment.
-
Reliable Performance: Built to operate under harsh industrial conditions with consistent output reliability.
Frequently Asked Questions (FAQ)
-
What is the maximum current per channel for the ADV551-P03?
Each output channel supports up to 0.5 A. -
Is the ADV551-P03 compatible with ProSafe-RS systems?
Yes, it can be used in safety-instrumented systems like ProSafe-RS when appropriately certified. -
How are outputs isolated in the ADV551-P03?
Each channel is individually isolated using photocoupler technology. -
Can I use the ADV551-P03 in high-temperature environments?
The module supports operation in temperatures up to 55°C. -
How is the ADV551-P03 powered?
Power is supplied through the base plate from the system cabinet. -
Is hot-swapping supported for this module?
No, the ADV551-P03 does not support hot swapping. Power must be turned off before replacement. -
What kind of diagnostic features does it offer?
It provides channel failure detection and general module diagnostics. -
Can the ADV551-P03 be used in redundant configurations?
Yes, when installed in a system designed for redundancy, the module can operate with failover. -
What is the update time for the outputs?
The typical update time is less than or equal to 100 ms. -
Is the module suitable for safety-critical applications?
It can be used in safety applications when part of a certified ProSafe-RS configuration.
Related Models (Same Series or Compatible)
| Model | Description | Output Type | Channels | Notes |
|---|---|---|---|---|
| ADV551-P00 | Digital Output Module | Sink | 32 | Earlier version |
| ADV552-P03 | Digital Output Module (Source Type) | Source | 32 | Source output version |
| ADV561-P03 | Digital Output Module (16 channels) | Sink | 16 | Lower channel density |
| ADV161-P03 | Digital Input Module | – | 16 | Input version, same family |
| ADV151-P03 | Digital Input Module (32 channels) | – | 32 | Input counterpart |
| AAI543-H00 | Analog Input Module | – | 8 | Analog I/O from same platform |
Popular Yokogawa Models
| Model | Description | Type | Application |
|---|---|---|---|
| AAI543-H00 | Analog Input Module | Analog Input | Process signal acquisition |
| ADV151-P03 | Digital Input Module | Digital Input | Binary input processing |
| AAR181-S00 | Remote I/O Network Module | Network Interface | Remote system integration |
| AAI841-H00 | Analog Input (High Speed) | Analog Input | Fast signal acquisition |
| CP451-10 | Processor Module | CPU | Main controller for CENTUM VP |
| PW482-10 | Power Supply Module | Power | Cabinet-mounted power unit |