Company Information | ||||||||
[email protected] | ||||||||
Mobile | +8613666033393 | |||||||
+8613666033393 | ||||||||
13666033393 | ||||||||
Add | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China |
Product Overview
The Honeywell 900H02-0001 is a 16-channel DC digital output module used in the ControlEdge HC900 system. It features intelligent power switching with galvanic isolation, electronic protection, and diagnostic indicators for enhanced reliability in industrial automation environments.
Technical Specifications
Parameter | Specification |
---|---|
Module Type | Digital Output (DC, current sinking) |
Output Channels | 16 (in 2 groups of 8) |
Output Type | Intelligent Power Switch (IPS) |
Operating Voltage | 6.5 to 32 VDC (5.0–6.5 V @ <0.5A) |
Peak Voltage | 34 VDC |
Output Current | Max 1 A/point, 8 A total resistive load |
Inrush Current | 4 A for 10 ms |
ON Voltage Drop | 0.3 VDC @ 1 A |
Leakage Current | Max 0.15 mA @ 32 VDC |
Output Protection | Electronic overload (current & temperature) |
ON/OFF Response Time | 6 ms / 6 ms |
Galvanic Isolation | 2 groups of 8 outputs |
Power Consumption | 5V: 340 mA; 24V: 0 mA |
Dimensions (H x W x D) | 137 x 35.6 x 137.16 mm |
Weight | 0.425 kg |
Applications
-
Factory automation systems
-
Burner and boiler control
-
Material handling systems
-
Batch and continuous process control
-
Water treatment and utilities
-
Safety interlock signaling
Product Advantages
-
Modular design fits ControlEdge HC900 racks
-
Electronic protection ensures durability under overload
-
Galvanic isolation between output groups prevents cross-interference
-
Real-time diagnostics with status LEDs for each channel
-
Hot-swappable module for ease of maintenance
-
Compact footprint suitable for space-constrained cabinets
Frequently Asked Questions (FAQ)
Q1: What is the max load current per channel?
A1: 1 A per point for resistive load.
Q2: Is the module protected from overload?
A2: Yes, it has electronic current and thermal overload protection.
Q3: Can the module be replaced while powered?
A3: Yes, hot-swap is supported with appropriate terminal block disconnection.
Q4: What is the minimum load requirement?
A4: 0 mA, making it suitable for low-power signaling.
Q5: Is each output channel galvanically isolated?
A5: No, isolation is per group of 8 outputs, not per point.
Q6: What diagnostics are available?
A6: Each output has a green LED; the module has green (active), amber (forced), and red (fault) indicators.
Q7: What is the peak voltage rating?
A7: 34 VDC.
Q8: Does it support AC output?
A8: No, it supports only DC (sinking type).
Q9: What is the response time?
A9: 6 ms both for OFF to ON and ON to OFF transitions.
Q10: What are typical application voltages?
A10: 24 VDC is most commonly used.
Related ControlEdge Series Models
Model Number | Description | Channels | Voltage Range | Weight | Dimensions (mm) |
---|---|---|---|---|---|
900H01-0202 | Relay Output Module | 8 | 120/240 VAC | 0.425 kg | 137 x 35.6 x 137.16 |
900H03-0202 | Digital Output, AC (120/240 VAC) | 8 | 80–264 VAC | 0.230 kg | 137 x 35.6 x 137.16 |
900H32-0102 | Digital Output, DC (Sourcing) | 32 | 10–32 VDC | 0.180 kg | 137 x 35.6 x 137.16 |
900G01-0202 | Digital Input, Contact | 16 | 15 VDC | 0.354 kg | 137 x 35.6 x 137.16 |
900G32-0101 | Digital Input, DC (Sinking) | 32 | 10–32 VDC | 0.175 kg | 137 x 35.6 x 137.16 |
900A01-0202 | Analog Input, Universal | 8 | Various | 0.210 kg | 137 x 35.6 x 137.16 |
Popular Honeywell Models
Model Number | Description | Channels | Voltage Range | Weight | Dimensions (mm) |
---|---|---|---|---|---|
900C30-0460 | Controller, Compact | – | – | 0.350 kg | 137 x 38.1 |
900B08-0202 | Analog Output Module, 8 Ch | 8 | 0–21 mA | 0.400 kg | 137 x 35.6 x 137.16 |
900A16-0103 | Analog Input Module, 16 Ch High Lvl | 16 | V/mA | 0.397 kg | 137 x 35.6 x 137.16 |
900S50-0460 | Scanner Module, 1 Port | – | – | 0.360 kg | 137 x 38.1 |
900P01-0301 | Power Supply, 120/240VAC | – | 90–264 VAC | 0.820 kg | 137 x 72.6 |
900PSM-0200 | Power Status Module | – | – | 0.448 kg | 137 x 35.6 |